KNL1 series Residual current circuit breaker(without over-current protection) is suitable for the line of AC,A and S 50/60Hz, voltage 240V(2 pole)/415V(4 pole), rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will cut off the power rapidly to protect human safety and prevent the accident due to the current leakage. It can be used as infrequent changeover of the line in normal situation.It is applicable to industrial site, commercial site, tall building and civil house.
It complies with standard of GB16916.1 and IEC/EN61008.1.
KNL1 series Residual current circuit breaker(without over-current protection) is suitable for the line of AC,A and S 50/60Hz, voltage 240V(2 pole)/415V(4 pole), rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will cut off the power rapidly to protect human safety and prevent the accident due to the current leakage. It can be used as infrequent changeover of the line in normal situation.It is applicable to industrial site, commercial site, tall building and civil house.
It complies with standard of GB16916.1 and IEC/EN61008.1.
Frame class | 63A |
Rated working voltage | 240V/415V |
Rated frequency | 50/60Hz |
Rated working current | 1、3、6、10、16、20、25、32、40、50、63A |
Making and breaking capacity | 6000A(6~40A),4500A(50、63A) |
Release type | B、C、D |
Poles | 1、2、3、4P |
Mechanical life | 20000 |
Electric life | 4000 |
Sequence NO . | Release | Test current I/In | Start state | Tripping time | Expected result |
1 | B、C、D | 1.13In | Cold state | t≤1h | Not tripping |
2 | B、C、D | 1.45In | Start right after the serial NO . 1 test | t<1h | Tripping |
3 | B、C、D | 2.55In | Cold state | 1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) | Tripping |
4 | B C D | 3In 5In 10In | Cold state | t≤0.1s | Not Tripping |
5 | B C D | 5In 10In 20In | Cold state | t<0.1s | Tripping |
Frame class | 63A |
Rated working voltage | 240V/415V |
Rated frequency | 50/60Hz |
Rated working current | 1、3、6、10、16、20、25、32、40、50、63A |
Making and breaking capacity | 6000A(6~40A),4500A(50、63A) |
Release type | B、C、D |
Poles | 1、2、3、4P |
Mechanical life | 20000 |
Electric life | 4000 |
Sequence NO . | Release | Test current I/In | Start state | Tripping time | Expected result |
1 | B、C、D | 1.13In | Cold state | t≤1h | Not tripping |
2 | B、C、D | 1.45In | Start right after the serial NO . 1 test | t<1h | Tripping |
3 | B、C、D | 2.55In | Cold state | 1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) | Tripping |
4 | B C D | 3In 5In 10In | Cold state | t≤0.1s | Not Tripping |
5 | B C D | 5In 10In 20In | Cold state | t<0.1s | Tripping |