Technical parameter
| Frame class | 125A |
| Rated working voltage | 240/415V |
| Rated frequency | 50/60Hz |
| Rated working current | 63, 80, 100, 125 |
| Making and breaking capacity | 10KA(63,80,100A), 6KA(125A) |
| Release type | B, C, D |
| Poles | 1, 2, 3, 4P |
| Mechanical life | 20000 |
| Electric life | 2000 |
The over-current tripping unit protection feature
| Sequence NO. |
Release | Test current I/In | Start state | Tripping time | Expected result |
||
| IEC60898-1 | IEC60947-2 | IEC60898-1 | IEC60947-2 | ||||
| 1 | C、D | 1.13In | 1.05In | Cold state | t≤1h(In≤63A) t≤2h(In>63A) |
t≤1h(In≤63A) t≤2h(In>63A) |
Not tripping |
| 2 | C、D | 1.45In | 1.3In | Start right after the serial NO. 1 test |
t<1h(In≤63A) t<2h(In>63A) |
t<1h(In≤63A) t<2h(In>63A) |
Tripping |
| 3 | C、D | 2.55In | — | Cold state | 1s<t<60s (In≤32A) 1s<t<120s (In>32A) |
Tripping | |
| 4 | C D |
5In 10In |
8In | Cold state | t≤0.1s | t≤0.2s | Not tripping |
| 5 | C D |
10In 20In |
12In | Cold state | t<0.1s | t<0.2s | Tripping |
Dimensions(mm)