KNBL1-32 RCCB With Over Current Protection

KNBL1-32 series leakage breaker is suitable for the leakage protection of the line of AC,A and S 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
KNBL1-32 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as well as infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.

Frame class 32A
Rated working voltage 240V
Rated frequency 50/60Hz
Rated working current 6、10、16、20、25、32A
Rated residual operating current 30mA、10mA
Maximum operating time I△n   t≤0.3s , 5I△n   t≤0.04s
Making and breaking current 4500A
Release type C
Poles 1P+N
Mechanical life 8000
Electric life 4000

 

Sequence NO . Release Test
current I/In
Start state Tripping time Expected result
1 C 1.13In Cold state t≤1h Not tripping
2 C 1.45In Start right after the serial NO . 1 test t<1h Tripping
3 C 2.55In Cold state 1s<t<60s Tripping
4 C 5In Cold state t≤0.1s Not Tripping
5 C 10In Cold state t<0.1s Tripping