Technical parameter
| Frame class | 63A |
| Rated working voltage | 240V |
| Rated frequency | 50/60Hz |
| Rated working current | 6, 10, 16, 20, 25, 32, 40, 50, 63A |
| Rated residual operating current | 0.01, 0.03, 0.1, 0.3A |
| Rated residual un-operating current | 0.5IΔn |
| Sensitivity | A Type, AC Type |
| Maximum operating time | IΔn t<0.3s, 5IΔn t<0.04s |
| Instant release type | B, C, D Type |
| Rated limiting short-circuit current | 6000A |
| Pole number | 2P |
| Mechanical life | 20000 |
| Electric life | 4000 |
The over-current tripping unit protection feature
| Sequence NO. |
Release | Test current I/In |
Start state | Tripping time |
Expected result |
| 1 | C | 1.13In | Cold state | t≤1h | Not tripping |
| 2 | C | 1.45In | Start right after the serial NO.1 test | t<1h | Tripping |
| 3 | C | 2.55In | Cold state | 1s<t<60s(In≤32A) 1s<t<120s(In>32A) |
Tripping |
| 4 | C | 3In 5In 10In |
Cold state | t≤0.1s | Not tripping |
| 5 | C | 5In 10In 20In |
Cold state | t<0.1s | Tripping |
Dimensions(mm)

Privacy Policy | SiteMap