KNLN5-63 Series 240V Single Phase RCBO

KNLN5-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage. KNLN5-63 series leakage breaker can protect against overload and short-circuit. It can be used as well as infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.

Technical parameter

Frame class 63A
Rated working voltage 240V
Rated frequency 50/60Hz
Rated working current 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated residual operating current 0.01, 0.03, 0.1, 0.3A
Rated residual un-operating current 0.5IΔn
Sensitivity A Type, AC Type
Maximum operating time IΔn t<0.3s, 5IΔn t<0.04s
Instant release type B, C, D Type
Rated limiting short-circuit current 6000A
Pole number 2P
Mechanical life 20000
Electric life 4000

 

The over-current tripping unit protection feature

Sequence
NO.
Release Test
current I/In
Start state Tripping
time
Expected
result
1 C 1.13In Cold state t≤1h Not tripping
2 C 1.45In Start right after the serial NO.1 test t<1h Tripping
3 C 2.55In Cold state 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
Tripping
4 C 3In
5In
10In
Cold state t≤0.1s Not tripping
5 C 5In
10In
20In
Cold state t<0.1s Tripping

 

Dimensions(mm)